Hyundai Residual Current Circuit Breaker RCCB 3P+N 30/100mA Type A – 16A/40A, IEC 61008-1
Hyundai HRC63S RCCB 3P+N, Type A
The Hyundai HRC63S monitors three-phase circuits with a neutral conductor for dangerous residual currents. The four-pole design switches three phase conductors and the neutral conductor located on the left. Depending on the version, a rated current of 16 or 40 A and a rated residual current of 30 or 100 mA are available.
As a Type A, the RCCB detects sinusoidal AC and pulsating DC residual currents. A test button allows for regular functional checks. Two indicators separately display the switching state and residual current tripping.
Advantages
- Four-pole design for 3P+N circuits
- Type A residual current detection
- Versions with 16 or 40 A
- Versions with 30 or 100 mA rated residual current
- Neutral conductor on the left
- Conditional short-circuit current up to 10 kA
- Test button and separate status indicators
- Dual terminals for cables and busbars
- Mounting on 35 mm DIN rail
- Tested according to IEC/EN 61008-1
Technical Data
| Model | HRC63S |
| Reference standard | IEC/EN 61008-1 |
| Number of poles | 4P, for 3P+N |
| Neutral conductor position | Left |
| Rated current (In) | 16 or 40 A |
| Rated voltage (Ue) | 240/415 V AC |
| Rated frequency | 50/60 Hz |
| Conditional short-circuit current (Inc) | 10 kA |
| Rated residual current (IΔn) | 30 or 100 mA |
| Residual current type | Type A |
| Rated making and breaking capacity (Im) | At least 500 A |
| Tripping time | 1 × IΔn < 300 ms; 5 × IΔn < 40 ms |
| Rated insulation voltage (Ui) | 690 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Dielectric strength | 2.5 kV |
| Electrical / mechanical service life | 10,000 / 20,000 cycles |
| Operating temperature | −40 °C to +55 °C |
| Air humidity | 95 % RH |
| Connection cross-section (max.) | 25 mm² |
| Tightening torque | 2.5 Nm |
| Vibration resistance | 3 g |
| Shock resistance | 40 mm free fall |
| Protection rating | IP20 |
| Contact indicator | Red = ON, Green = OFF |
| Net weight | 0.310 kg |
| Dimensions (H × D × W) | 81 × 74 × 71.6 mm |
| Mounting | Clip mounting on DIN rail, 35 × 7.5 mm |
| Installation position | Vertical or horizontal |
| Housing | Flame-retardant thermoplastic |
| Busbar connection | Pin or fork type |
Produktsicherheit & Herstellerangaben
Hersteller
HD Hyundai Electric Co., Ltd.
477, Bundangsuseo-ro, Bundang-gu
13553 Seongnam-si, Gyeonggi-do
Republik Korea
Importeur und verantwortliche Person in der EU
OAM GmbH
Rotenturmstraße 16–18 / 1 / 6. OG
1010 Wien, Österreich
office@hdeon.com
Produktkennzeichnung
Marke: HYUNDAI ELECTRIC
Artikelnummer: HRC63S4PG4S0000C00016F
EAN: 8809617437450
CE-gekennzeichnet
Sicherheitshinweise
- Montage, Anschluss und Inbetriebnahme nur durch eine Elektrofachkraft unter Beachtung der geltenden Errichtungsbestimmungen (z. B. ÖVE/ÖNORM E 8101, DIN VDE 0100).
- Vor allen Arbeiten die Anlage spannungsfrei schalten, gegen Wiedereinschalten sichern und die Spannungsfreiheit feststellen.
- Nur innerhalb der angegebenen technischen Daten (Nennspannung, Nennstrom, Schaltvermögen) einsetzen.
- Beschädigte Geräte nicht installieren oder weiter betreiben. Das Gerät nicht öffnen oder verändern.
- Montage- und Bedienungsanleitung des Herstellers beachten und aufbewahren.