Hyundai RCBO 2-pole for phase + neutral, 6kA 30mA Type A – B/C, 10–25A
Hyundai HRO63A RCBO, 2-pole for phase and neutral
The Hyundai HRO63A combines residual current, overload, and short-circuit protection in a two-pole RCBO. It is designed for single-phase circuits with phase and neutral conductors and switches both poles. Depending on the version, rated currents from 10 to 25 A as well as B or C tripping characteristics are available.
With a 30 mA rated residual current and Type A residual current detection, the RCBO is suitable for the protection of people and circuits. Type A detects sinusoidal AC and pulsating DC residual currents.
Advantages
- Residual current, overload, and short-circuit protection in one device
- Two-pole design for phase and neutral
- 6 kA short-circuit breaking capacity
- 30 mA rated residual current and Type A residual current detection
- Versions with 10, 13, 16, 20, or 25 A
- Tripping characteristic B or C
- Mounting on 35 mm DIN rail
- Tested according to IEC/EN 61009-1
Technical Data
| Model | HRO63A |
| Reference standard | IEC/EN 61009-1 |
| Number of poles | 2P, both poles switched |
| Application | Phase and neutral |
| Operating mode | Electronic |
| Rated current (In) | 10, 13, 16, 20, or 25 A |
| Rated voltage (Ue) | 240 V AC |
| Rated frequency | 50/60 Hz |
| Short-circuit breaking capacity (Icn) | 6 kA, Ics = 100 % Icn |
| Rated residual current (IΔn) | 30 mA |
| Tripping characteristics | B: 3–5 × In; C: 5–10 × In |
| Residual current type | Type A |
| Rated breaking capacity (IΔm) | 4.5 kA |
| Tripping time | 1 × IΔn < 300 ms; 5 × IΔn < 40 ms |
| Rated insulation voltage (Ui) | 500 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Dielectric strength | 2.5 kV |
| Electrical / mechanical lifespan | 10,000 / 20,000 switching cycles |
| Operating temperature | −25 °C to +55 °C |
| Humidity | 95 % RH |
| Energy limiting class | 3 |
| Terminal cross-section (max.) | 25 mm² |
| Tightening torque | 2 Nm |
| Vibration resistance | 3 g |
| Shock resistance | 40 mm free fall |
| Degree of protection | IP20 |
| Contact indicator | Red = ON, Green = OFF |
| Weight | 0.258 kg |
| Dimensions (H × D × W) | 83 × 71.7 × 35.6 mm |
| Mounting | Clip-on mounting on DIN rail, 35 × 7.5 mm |
| Installation position | Vertical or horizontal |
| Housing | Flame-retardant thermoplastic |
| Certification | INTERTEK CB |
Produktsicherheit & Herstellerangaben
Hersteller
HD Hyundai Electric Co., Ltd.
477, Bundangsuseo-ro, Bundang-gu
13553 Seongnam-si, Gyeonggi-do
Republik Korea
Importeur und verantwortliche Person in der EU
OAM GmbH
Rotenturmstraße 16–18 / 1 / 6. OG
1010 Wien, Österreich
office@hdeon.com
Produktkennzeichnung
Marke: HYUNDAI ELECTRIC
Artikelnummer: HRO63A2PG4B0000C00010F
EAN: 8809791046486
CE-gekennzeichnet
Sicherheitshinweise
- Montage, Anschluss und Inbetriebnahme nur durch eine Elektrofachkraft unter Beachtung der geltenden Errichtungsbestimmungen (z. B. ÖVE/ÖNORM E 8101, DIN VDE 0100).
- Vor allen Arbeiten die Anlage spannungsfrei schalten, gegen Wiedereinschalten sichern und die Spannungsfreiheit feststellen.
- Nur innerhalb der angegebenen technischen Daten (Nennspannung, Nennstrom, Schaltvermögen) einsetzen.
- Beschädigte Geräte nicht installieren oder weiter betreiben. Das Gerät nicht öffnen oder verändern.
- Montage- und Bedienungsanleitung des Herstellers beachten und aufbewahren.