Hyundai MCCB moulded case circuit breaker HGP400X 3P 150kA – 300–400A, adjustable overload and short circuit, IEC 60947-2
Pickup currently not available
Hyundai HGP400X-H moulded case circuit breaker (MCCB), 3-pole, 150 kA
The Hyundai HGP400X is a 3-pole moulded case circuit breaker in the 400 AF frame with 150 kA breaking capacity for incoming feeders and main distribution boards with high currents. Overload and short-circuit settings are adjustable separately.
Features
- Versions 300 and 400 A
- Short-circuit setting adjustable from 5 to 10 × In
- 35 kA even at 660/690 V AC
- Breaking capacity 150 kA at 400/415 V (category X), Ics = 100 % Icu
- Thermal magnetic trip unit with adjustable overload protection
- Rated insulation voltage 1,000 V, operational voltage up to 690 V AC
- Front connection with screw terminals for switchgear and distribution boards
- Accessories available: auxiliary and alarm switch, shunt and undervoltage release, rotary handle and motor operator
Technical data
| Model | HGP400X-H |
| Standard | IEC/EN 60947-2, CE |
| Poles | 3P |
| Frame size | 400 AF |
| Rated current In | 300 or 400 A |
| Trip unit | Thermal magnetic MTM-63-JJ |
| Overload setting Ir | 0,8 – 0,9 – 1,0 × In |
| Instantaneous setting Ii | 5 – 6 – 7 – 8 – 9 – 10 × In (adjustable) |
| Breaking capacity Icu 380/415 V AC | 150 kA |
| Breaking capacity Icu 440/460 V AC | 150 kA |
| Breaking capacity Icu 480/500 V AC | 100 kA |
| Breaking capacity Icu 660/690 V AC | 35 kA |
| Breaking capacity Icu 220/240 V AC | 200 kA |
| Breaking capacity Icu 250 V DC | 100 kA |
| Service breaking capacity Ics | 100 % Icu |
| Rated insulation voltage Ui | 1,000 V |
| Rated operational voltage Ue | up to 690 V AC |
| Rated impulse withstand voltage Uimp | 8 kV |
| Frequency | 50/60 Hz |
| Reference temperature | 40 °C |
| Connection | Front connection, screw terminal |
| Mechanical endurance | 20,000 operations |
| Electrical endurance (440 V) | 6,000 operations |
| Dimensions (W × H × D) | 140 × 260 × 110 mm |
| Weight | 5.4 kg |
| Matching motor operator | MOT63GP |
Installation by a qualified electrician only. Isolate the installation before any work.
Product Safety & Manufacturer Information
Hersteller
HD Hyundai Electric Co., Ltd.
477, Bundangsuseo-ro, Bundang-gu
13553 Seongnam-si, Gyeonggi-do
Republic of Korea
Importeur und verantwortliche Person in der EU
OAM GmbH
Rotenturmstraße 16–18 / 1 / 6th Floor
1010 Vienna, Austria
office@hdeon.com
Produktkennzeichnung
Marke: HD HYUNDAI ELECTRIC
Artikelnummer: HGP400X3PT4S0000C00300H
EAN: 8809857964204
CE-gekennzeichnet
Sicherheitshinweise
- Montage, Anschluss und Inbetriebnahme nur durch eine Elektrofachkraft unter Beachtung der geltenden Errichtungsbestimmungen (z. B. ÖVE/ÖNORM E 8101, DIN VDE 0100).
- Vor allen Arbeiten die Anlage spannungsfrei schalten, gegen Wiedereinschalten sichern und die Spannungsfreiheit feststellen.
- Nur innerhalb der angegebenen technischen Daten (Nennspannung, Nennstrom, Schaltvermögen) einsetzen.
- Beschädigte Geräte nicht installieren oder weiter betreiben. Das Gerät nicht öffnen oder verändern.
- Montage- und Bedienungsanleitung des Herstellers beachten und aufbewahren.